EPCOM Certified Products
We test, inspect and restore all EPCOM products to working conditions.
Stock | Classification | Your Price |
---|
Product Specifications
AL1024ULXB2 UL Listed Sub-Assembly power supply/charger converts 115VAC, 60Hz input into a single 24VDC non power-limited output. It also offers a suite of features that includes AC fail supervision, battery presence, and low battery supervision.Input 115VAC / 60Hz, 4.2A.
Output
24VDC output.
8A continuous supply current with 10A supply current during alarm.
Filtered and electronically regulated output.
Short circuit and thermal overload protection.
Maximum Ripple: 250mV P/P
Battery Backup
Built-in charger for sealed lead acid or gel type batteries.
Automatic switch over to stand-by battery when AC fails.
Zero voltage drop when switched over to battery backup.
Visual Indicators
AC input and DC output LED indicators.
Supervision
AC fail supervision (form "C" contacts).
Notification trigger is selectable for 30 seconds (factory set) or 6 hours.
Low battery and battery presence supervision (form "C" contacts).
Electrical
Temperature:
Operating: 0° C to 49° C (32° F to 120° F).
Storage: - 20° C to 70° C ( - 4° F to 158° F).
Relative Humidity 85% +/- 5%.
BTU/Hr (approx.): 123 BTU/Hr.
System AC input VA requirement: 483VA
Dimensions (approximate):
- 4.505"W x 8.4"L x 1.955"H (114.427 mm W x 213.36 mm L x 49.657 mm H).
Weights (approximate):
- Product Weigtht: 1.15 Lbs. (0.52 kg).