DIN Rail Mounted DC Surge Protection Device, Designed With MOV Technology To Meet Type 2 Requirments
Contact your Sales Executive to obtain your first password.
EPCOM Certified Products
We test, inspect and restore all EPCOM products to working conditions.
Stock | Classification | Your Price |
---|
Optional Accessories
Product Specifications
DIN rail mounted DC surge protection device, designed with MOV technology to meet Type 2 requirements. Equipped with suppression status visual indication and electrically isolated ‘Form C” dry contacts to allow remote monitoring.
Main Technical Data
Electrical Performance
- Number Of Ports Single port device
- Technology MOV
- Nominal Operating Voltage Un 1000 Vdc
- Maximum Continuous Operating Voltage Uc 1350 Vdc
- Nominal Discharge Current In (8x20μs) 20 kA
- Maximum Discharge Current Imax (8x20μs) Type 2 40 kA
- Voltage Protection Level Up 5 kV
- Response Time < 25 ns
- Recommended Over-Current Protection Device 32 A circuit breaker with C tripping characteristic (per IEC 60364-4-43)
- Status Indication Visual indication: Black = Normal, Red = Replace
- 3 pin contact switch for remote annunciation
- Maximum Contact Switch Rating 250 Vac / 1 A
Mechanical
- Location Category Indoor only
- Method of Mounting Fixed 35mm DIN rail
- Dimension (H x W x D) 90 mm x 54 mm x 68 mm (3.6” x 2.2” x 2.7”)
- Weight (Max) 0.33 kg (0.74 lb)
- Maximum Wire Size 25 mm2 (#4 AWG)
- Stripping Length Terminals 10 mm (0.375”)
- Torque Terminals 4.5 Nm (3.3 ft-lb)
- Maximum Wire Size Contacts 1.5 mm2 (#16 AWG)
- Stripping Length Contacts 7 mm (0.25”)
- Torque Contacts 1 Nm (0.75 ft-lb)
Environmental
- Operating Temperature -40°C to +70°C
- Relative Humidity ≤ 95% non condensing
- Enclosure Protection Level IP20
- Housing Inflammability Rating PA66, UL94 V-0
- Certifications RoHS compliant