Contact your Sales Executive to obtain your first password.
EPCOM Certified Products
We test, inspect and restore all EPCOM products to working conditions.
Stock | Classification | Your Price |
---|
Product Specifications
The GD-2A is a low voltage electronic detector of combustible, heating type gases. The GD-2A is designed for connection to UL Listed Fire Alarm/Burglary Control Panels. Alarm control panels that work on 12 or 24 VDC can provide battery backup to the GD-2A detectors. This product is for use in ordinary indoor locations of family living units and office workspaces. The GD-2A is intended for installation in buildings in non-hazardous locations such as residences, retail stores, office buildings, and institutional buildings. This combustible gas detector has been evaluated by UL for natural gas and LP gas.
Features
- Supervised Sensor
- Simple installation and operation
- SPDT Alarm and N.C. Trouble Relay
- Can be self-restoring or latching
- California State Fire Marshal Listed
- Solid State Electronic sensors: no maintenance or recalibration
- Sensitivity tested based on UL 1484 Standard for Residential Gas Detectors
- Listed to UL Standard 2075 for the Standard for Safety for Gas and Vapor Detector and Sensors
- Size: 4 ½ x 5 x 1 5/8 inches
- Shipping Weight: 0.54 pound
- Voltage: 12 to 24 VAC or VDC
- Current (non-alarm): 45 mA @ 12 VDC, 22 mA @ 24 VDC, 65 mA @ 12 VAC, 45 mA @ 24 VAC
- Current (in alarm): 70 mA @ 12 VDC, 35 mA @ 24 VDC, 100 mA @ 12 VAC, 65 mA @ 24 VAC
- Color: white
- Sensor Maintenance: not required
- Alarm Relay Rating: 0.125 A, 40 V, 3 VA
- Trouble Relay: 0.250 A, 40 V, 10 VA
- Operating Temperature Range: 32° to 120° F
- Alarm Set Point: Per UL 1484, 25% LEL
Note:_ Do NOT mount the GD-2A in kitchen or bathrooms
The use of alcohols, ammonia, cleaning solvents, paint thinner, gasoline vapors,
and aerosol propellants ( aerosol cans such as hair spray usually contain a combustible gas )
may cause alarms