Contact your Sales Executive to obtain your first password.
EPCOM Certified Products
We test, inspect and restore all EPCOM products to working conditions.
Stock | Classification | Your Price |
---|
Product Specifications
• Power: 3 W (max) from 12 to 24 VAC or 12 to 32 VDC
• Current @ 24 VDC: 75 mA in alarm, 50 mA fan relay on and 23 mA stand by
• Shipping Weight: 1 pound (0.45 kg)
• Size: 4 1/2 x 4 x 2 1/8 in. (11.4 X 10.2 X 5.4 cm)
• Color: Dark gray • Connections: plugs/terminals
• Mounting Box: (not included) 4x4 electrical
• Fan Relay: 5 A, 240 VAC, pilot duty, SPDT, latching or non-latching
• Fan Relay Actuation: selectable at “dIS” (disabled), 15 ppm, 25 ppm, 35 ppm (default), 50 ppm or 100 ppm
• Fan Delay Settings: 0, 1, 3 (default), 5 and 10 minutes
• Fan Relay Minimum Runtime Settings: 0 (default), 3, 5, 10 or 15 minutes
• Alarm Relay: 0.5A 120 V, 60 VA
• Alarm Relay Actuation: selectable N.O. default or N.C.
• Alarm Relay Settings: dIS, 50 ppm, 100 ppm, 150 ppm and 200 ppm (default)
• Current Loop: 4-20 mA for 0-200 ppm
• Operating Environment: 0°F to 125° F (-18°C to 52°C),10 to 90% RH non-condensing
Carbon Monoxide Detector and Controller
The MACURCO CM6 is a low voltage detector, controller and transducer, with a built-in double relay, selectable output, selectable output from 4-20 mA, buzzer and digital screen, is an electronic detection system used to measure the concentration of CO and provide feedback and control the automatic fan/extractor to reduce the concentration of CO in parking lots, maintenance areas and other commercial applications.
Features:
- UL list
- Mounting standard electrical box 4 "x 4"
- Factory calibrated
- Activation of the selectable fan relay in 15, 25, 35 (by default), 50 or 100 ppm of CO
- Capable of showing concentrations of CO in the range of 0 to 200 ppm
- Alarm relay of NA or NC @ 0.5 A
-Fan relay: SPDT @ 5 A
- Design of supervised system: a problem in the detector will activate the fan and alarm
- Dimensions: 114 X 102 X 54 mm