Product Specifications
Input:
• Power input 120VAC 60 Hz, 5 amp.
• Two (2) Class A, Style Z or two (2) Class B, Style W, Y FACP inputs.
• Two (2) NC dry contact trigger inputs.
Output:
• Class 2 Rated power limited outputs.
• 24VDC @10 amp max total alarm current.
• 2.5 amp max current per output.
• Separate 1.0 amp auxiliary output.
• Programmable supervised indicating circuit outputs: Four (4) Class B, Style W, Y or Two (2) Class A, Style Z or One (1) Class A, Style Z and Two (2) Class B, Style W, Y.
• Thermal and short circuit protection with auto reset.
Battery Backup:
• Built-in charger for sealed lead acid or gel type batteries.
• Automatic switchover to stand-by battery when AC Fails.
• Zero voltage drop when switching over to battery backup.
Supervision:
• AC fail supervision (form “C” contact, 1 amp / 28VDC).
Factory set for 30 seconds with an optional 2.5 to 3-hour
delay setting (field selectable).
• Instant local AC trouble reporting relay
(form “C” contact, 1 amp / 28VDC).
• Battery presence and low battery supervision
(form “C” contact, 1 amp / 28VDC).